Manufacturer of Petroleum Test Equipment since 1873

Product   

 Portable Particle Counter for aviation turbine fuels

Technical Data

Test time: 2 minutes
Flow Rate: 25-50 ml/min
Fluid Compatability: hydrocarbon fuel, mineral oil
Repeatability/Accuracy: as per or better than ISO 11 171
Principle of operation: optical scanning analysis and measurements of
actual particles and inference to water presence
Primary output: >4 / >6 / >14 / >21 / >25 / >30µm counts per ml
Secondary output: (diagnostic) % volume distribution, via graphical display
on handset and printout
Cleanroom standards: ISO 7-22 in acc. with ISO 4406-1999
Data entry: 32 character two line dot matrix LCD,
full alpha numeric entry
Data retrieval: memory access gives test search facility
Calibration: in acc. to ISO 11 171:1999, clause 6
Operating Temperature: +5°C to +80°C
Memory store: 300 test capacity
Computer interface: via RS 232 connection @ 9600 baud rate
(USB serial cable to RS 232 option available)
Laboratory sampling: oil delivery unit - test portion sampling device
Portability: battery pack and carrying case with wheels
Printer facility: integral 16 column printer for hard copy data
Certification: complies with all relevant EC declarations of conformity
Power requirements: 12 V DC, 6x 'D' cell or rechargeable batteries
Weight: 8 kg (13 kg incl. carrying case)
Power supply: 110-240 V, 50/60 Hz